Indesit C 64S G1 (X) I Bedienungsanleitung Seite 13

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 46
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 12
14
Installation
The following instructions should be read by a qualified
technician to ensure that the appliance is installed, regu-
lated and serviced correctly in compliance with current
standards.
Important: Remember to unplug the appliance from
the mains before making adjustments or doing main-
tenance.
Positioning
Important: This unit may be installed and used only in
permanently ventilated rooms in compliance with current
National Regulations. The following requirements must be
observed:
a) The room must be equipped with an exhaust system
that vents the combustion fumes to the outside. It may
consist of a hood or an electric fan that automatically
starts each time the appliance is turned on.
Flue or Branched Flue System Directly to the Outside
(only for cooking appliances)
b) The room must also have a system to permit proper air
circulation, needed for combustion to occur normally.
The flow of air needed for combustion must not be less
than 2 m
3
/h per kW of installed power. The air circula-
tion system may take air directly from the outside by
means of a pipe with an inner cross section of at least
100 cm
2
; the opening must not be able to be acciden-
tally blocked. For those appliances not equipped with a
safety device for accidental flame loss, the ventilation
apertures must be increased by 100%, with the mini-
mum being 200 cm
2
(Fig. A). The system can also pro-
vide the air needed for combustion by indirect means,
i.e. from adjacent rooms fitted with air circulation tubes
as described above. However, these rooms must not
be common rooms or bedrooms. (Fig. B)
.
Detail A Adjacent Room to
Room be Ventilated
A
Examples of Ventilation Openings Increased Opening Between
Comburent Air Door and Floor
Fig. A Fig. B
c) Intensive and prolonged use of the appliance may re-
sult in the need for supplemental air circulation, e.g.
opening windows or increasing mechanical venting (if
present).
d) Liquified petroleum gas is heavier than the air and, there-
fore, settles downwards. Thus, rooms containing LPG
cylinders must also be equipped with apertures to the
outside for ventilation of gas in the case of leaks. LPG
cylinders must not, therefore, be installed or stored in
rooms or storage areas that are below ground level (cel-
lars, etc.) whether they are partially or completely full.
It is a good idea to keep only the cylinder being used in
the room, positioned so that it is not subject to heat
produced by external sources (ovens, fireplaces, stoves,
etc. ) which are able to increase the temperature of the
cylinder above 50°C.
Levelling Your Appliance (only on certain models)
4 support feet which are adjusted using screws are located
in the lower part of the cooker. These level off the oven
when necessary. It is essential that the cooker be standing
level.
Mounting the legs (only on certain models)
Press-fit legs are supplied which fit under the base of your
cooker.
Installing the Cooker
The appliance can be installed next to cabinets, provided
they are not taller than the hob. If the cooker is placed in
contact with walls or the sides of adjacent cabinets, they
must be capable of withstanding a rise in temperature of
50°C above room temperature. For proper installation of
the cooker, the following precautions must be taken:
a) Kitchen cabinets installed next to the cooker that are
higher than the top of the hob, must be at least 600
mm from the edge of the hob itself.
b) Hoods must be installed according to the requirements
in the installation manual for the hood and, in any case,
at a minimum height of 650 mm.
c) If the hood is installed below a wall cabinet, the latter
Seitenansicht 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 45 46

Kommentare zu diesen Handbüchern

Keine Kommentare