Indesit PF 640 E (IX) U Bedienungsanleitung Seite 12

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 18
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 11
13
Installation Instructions for built-in
The following instructions are intended for the installer so
that the installation and maintenance procedures may be
followed in the most professional and expert manner possible.
Important: Disconnect the appliance from the electrical
supply before performing any maintenance or regulation
upkeep work.
Positioning the Cooktop
Important: this unit may be installed and used only in
permanently ventilated rooms in accordance with British
Standard Codes Of Practice: B.S. 6172 / B.S. 5440, Par. 2
and B.S. 6891 Current Editions. The following requirements
must be observed:
a) The room must be fitted with a ventilation system which
vents smoke and gases from combustion to the outside.
This must be done by means of a hood or electric
ventilator that turns on automatically each time the hood
is operated.
In a chimney stack or branched flue. Directly to the Outside
(exclusively for cooking appliances)
b) The room must also allow for the influx of the air needed
for proper combustion. The flow of air for combustion
purposes must not be less than 2 m³/h per kW of
installed capacity. The supply of said air can be effected
by means of direct influx from the outside through a
duct with a inner cross section of at least 100 cm² which
must not be able to be accidentally blocked. Those
appliances which are not fitted with a safety device to
prevent the flame from accidentally going out must have
a ventilation opening twice the size otherwise required,
i.e. a minimum of 200 cm² (Fig. A). Otherwise, the room
can be vented indirectly through adjacent rooms fitted
with ventilation ducts to the outside as described above,
as long as the adjacent rooms are not shared areas,
bedrooms or present the risk of fire (Fig. B).
Detail A Adjacent Room to be
Room Vented
A
Examples of ventilation holes Enlarging the ventilation slot
for comburant air. between window and floor.
Fig. A Fig. B
c) Intensive and prolonged use of the appliance may ne-
cessitate supplemental ventilation, e.g. opening a
window or increasing the power of the air intake system
(if present).
d) Liquidified petroleum gases are heavier than air and,
as a result, settle downwards. Rooms in which GPB-B
tanks are installed must be fitted with ventilation
openings to the outside in order to allow the gas to
escape in the event of a leak. Therefore, GPB-B tanks,
whether empty or partially full, must not be installed or
stored in rooms or spaces below ground level (cellars,
ect.). It is also a good idea to keep only the tank
currently being used in the room, making sure that it is
not near sources of heat (ovens, fireplaces, stoves,
etc.) that could raise the internal temperature of the
tank above 50°C.
Installation of Built-in Cooktops
Therefore, the appliance can be installed next to cabinets,
provided the height of the cabinet does not exceed that of
the hob. For proper installation of the cooktop, the following
guidlines must be followed:
a) If the cabinet(s) located next to the cooktop are higher
than the cooktop itself, the cabinet(s) must be installed at
least 110 mm from the edge cooktop;
b) Hoods must be installed in accordance with the
instructions contained in the installation manual for the
hoods themselves, and no less than 650 mm from the
cooktop;
c) In the case of the 600 mm cooker hoods, besides following
the recommendations in point b), the cabinets should be
positioned next to the hood at a height of at least 540 mm
from the top since this will make it possible to install the
lid and move it correctly. The cabinet should always be
installed at a height from the top which allows easy use
of pots and pans on the cooker.
d) Should the cooktop be installed directly under a cupboard,
the latter should be at least 700 mm (millimetres) from
the top, as shown in Figure.
600mm min.
540mm min.
700mm min.
e) The dimensions of the cutout for the appliance must be
those indicated in the figure. Clamps are provided to fasten
the cooktop to counters measuring from 20 to 40 mm in
thickness. To fasten the cooktop securely, it is
recommended that all the clamps be used.
Seitenansicht 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 18

Kommentare zu diesen Handbüchern

Keine Kommentare